INSTALLATION
Installation
24 | SHP-F 220-300 Premium www.stiebel-eltron.com
X0
2
L
L
N
N
PE
PE
L
N
PE
GNYE
BU
BN
1
1
2
X3
2
3
3
1
1
2
L1 / L2 / L3
N
A
B
D0000059152
A Power supply provided by power supply utility or energy
management system for switching the load (compressor)
B Power supply to impressed current anode and PCB
BN Brown
BU Blue
GNYE Green/yellow
Connect the electric cables for the separate impressed cur-
rent anode power supply to X0/1 and X0/2.
!
Material losses
The power supply to the impressed current anode must
be ensured at all times.
!
Material losses
With regard to the external switching device, the min-
imum runtime and minimum pause times must be ob-
served (see chapter "Appliance description/Minimum
runtime and minimum pause time").
10.5.3 Connection options: Operation with external signal
transmitter
!
Material losses
See "Permissible voltage range for external signal trans-
mitters" in chapter "Specification/data table".
Note
The appliance has a second, higher set temperature
which is selected at the factory. This is activated when
there is an external switching signal. Set temperature2 is
higher ranking than the standard set temperature while
there is an external switching signal.
An external signal transmitter for switching a separate set DHW
temperature (set temperature2) can be connected to terminal
X3/1-2. In the delivered condition, terminal X3/1-2 is not assigned.
If this terminal is connected at the voltage stated in the specifica-
tion (see "Permissible voltage range, external signal transmitter")
(L to X3/1, N to X3/2), the appliance enables set temperature2.
Following one-off activation (signal present for at least 1min-
ute), set temperature2 applies for at least 20minutes. When
the relevant DHW set temperature has been reached, the com-
pressor switches off and remains off for a minimum idle time of
20minutes.
The following diagram illustrates the connections by means of a
sample signal sequence from an external signal transmitter.
Example:
- Water temperature = 55 °C
- Set temperature 1 = 50 °C
- Set temperature 2 = 65 °C
1
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 t [min]
B
1
1
0 2
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 t [min]
D0000034613
A External signal
B Compressor
1 20 min. minimum runtime, set temperature2
2 20 min. minimum compressor idle time
Remove the appliance cover (see chapter "Cleaning and
maintenance/ Removing the appliance cover").
D0000061125
1
2
1 Strain relief
2 Terminal X3
Prepare the cables in such a way that each cable terminates
with a wire ferrule.
Push the cables through one of the cable entries in the appli-
ance casing.
Route the cables through the strain relief.
Connect the cables to X3.