INSTALLATION
Commissioning
26 | SHP-F 220-300 Premium www.stiebel-eltron.com
Standard system with 5m air duct (DN200) and two 90° bends
Length or
pce
Pressure drop per
m or per pce [Pa]
Pressure
drop [Pa]
Folded spiral-seam tube 5 0.67 3.35
90° bend (r = 1 * d) 2 2.3 4.6
Intake grille 2 6.2 12.4
Total 20.35
Set the fan output to 44% in the controller menu.
Note
If the air duct is longer or there are more bends, perform
the following individual system calculation.
Individual system calculation
Calculate the system pressure drop as the sum of all compo-
nents installed in the air duct.
Enter the calculated pressure drop on the X-axis of the dia-
gram. Read off the fan output from the Y-axis and adjust the
fan output parameter in the appliance menu.
Example 1 : Air duct diameter DN160
Length or
pce
Pressure drop per
m or per pce [Pa]
Pressure
drop [Pa]
Folded spiral-seam tube 10 2 20
90° bend (r = 1.5 * d) 0 4.5 0
90° bend (r = 1 * d) 3 5.5 16.5
Intake grille 2 6.2 12.4
Total 48.9
Example 2 : Air duct diameter DN200
Length or
pce
Pressure drop per
m or per pce [Pa]
Pressure
drop [Pa]
Folded spiral-seam tube 20 0.67 13.4
90° bend (r = 1.5 * d) 0 2.0 0
90° bend (r = 1 * d) 2 2.3 4.6
Intake grille 2 6.2 12.4
Intake expansion 1 5 5
Discharge reduction 1 2.8 2.8
Total 38.2
Table for your system
Length or
pce
Pressure drop per
m or per pce [Pa]
Pressure
drop [Pa]
Fan graph with examples showing how to calculate the necessary fan setting with a duct connection
35
40
45
50
55
60
65
0 10 20 30 40 50 60 70 80 90 100
D0000045294
1
Example 2 Example 1
X Pressure drop [Pa]
Y Fan setting [%]
1 Fan curve