The Parallel relay function can be used to opera-
te an allocated parallel relay alongside a selected
reference relay. With this function, e. g. a valve can
be controlled in parallel to the pump via a separate
relay.
If the Overrun option is activated, the parallel relay
remains switched on for the adjusted duration time
after the reference relay has been switched o.
If the Delay option is activated, the parallel relay
will be energised after the adjusted duration has
expired. If the reference relay is switched o again
during the delay time, the parallel relay will not be
switched on at all.
If the Inverted option is activated, the parallel relay
switches on when the reference relay switches o
and vice versa.
Adjustment channel Description Adjustment range / selection Factory setting
Relay Relay selection system dependent system dependent
Ref. relay Reference relay selection system dependent system dependent
Overrun Overrun option Yes, No No
Duration Overrun time 1 ... 30 min 1 min
Delay Delay option Yes, No No
Duration Delay time 1 ... 30 min 1 min
Inverted Inverted switching option Yes, No No
Funct. Activation / Deactivation Activ., Deactivated Deactivated
Arrangement / Opt. functions / Add new function... / Parallel relay
The mixer function can be used to adjust the actual
ow temperature to the desired mixer target tem-
perature TMixer. The mixer is opened or closed in
pulses depending on this deviation. The pulses are
determined by the adjustable Interval. The pause
is determined by the dierence between the actual
value and the set value.
The mixer runtime can either be adjusted in the
channel Runtime or automatically adapted with the
Oset function. When Oset is selected, the mixer
will close rst. When button
again. The time measured will
automatically appear as the value for the channel
Runtime.
Once per day, the mixer will automatically adjust its-
elf. The exact Time for that can be adjusted.
Mixer
Adjustment channel Description Adjustment range / selection Factory setting
Relay closed Relay selection mixer closed system dependent system dependent
Relay open Relay selection mixer open system dependent system dependent
Sensor Sensor selection system dependent system dependent
TMixer Mixer target temperature 0 ... 130 °C [32 ... 266 °F] 60 °C [140 °F]
Interval Mixer interval 1 ... 20 s 4 s
Runtime Mixer runtime 10 ... 600 s 240 s
Oset
Automatic adaption of the
mixer runtime
- -
Time Adjustment time 00:00 ... 23:30 23:30
Funct. Activation / Deactivation Activ., Deactivated Deactivated
Arrangement / Opt. functions / Add new function... / Mixer