Solid fuel boiler The solid fuel boiler function can be used for trans-
ferring heat from a solid fuel boiler to a store.
The allocated relay is energised when all switch-on
conditions are fullled:
the temperature dierence between the allocated
sensors has exceeded the switch-on temperature
dierence
the temperature at the solid fuel boiler sensor has
exceeded the minimum temperature
the temperature at the store sensor has fallen
below the maximum temperature
If Tset is exceeded, pump speed control will come
into eect. For every deviation of 2 K [4 °Ra], the
pump speed will be adjusted by 10 %.
Adjustment channel Description Adjustment range / selection Factory setting
Relay Relay selection system dependent system dependent
Sen. Boiler Solid fuel boiler sensor selection system dependent system dependent
Sen. Store Store sensor selection system dependent system dependent
Ton Switch-on temperature dierence 1.0 ... 30.0 K [2.0 ... 60.0 °Ra] 6.0 K [12.0°Ra]
To Switch-o temperature dierence 0.5 ... 29.5 K [1.0 ... 59.0 °Ra] 4.0 K [8.0°Ra]
Tset Set temperature dierence 1.5 ... 40.0 K [3.0 ... 80.0 °Ra] 10.0 K [20.0°Ra]
Min. speed Minimum speed 30 ... 100 % 30 %
Tmax St. Maximum temperature 10 ... 95 °C [50 ... 204 °F] 60 °C [140 °F]
Tmin boiler Minimum temperature 10 ... 95 °C [50 ... 204 °F] 60 °C [140 °F]
Funct. Activation / Deactivation Activ., Deactivated Deactivated
Arrangement / Opt. functions / Add new function... / Solid fuel boiler
Sensor Store
Relay
Sensor Solid fuel boiler
295931-36390-8667 SOM 8 plus_en.indb 53 20.10.2011 13:14:47