56
Return preheating
The return preheating function can be used for
transferring heat from a heat source to the heating
circuit return.
The allocated relay is energised when both switch-
on conditions are fullled:
the temperature dierence between the allocated
sensors has exceeded the switch-on temperature
dierence
the temperature at the outdoor temperature
sensor has fallen below the adjusted outdoor
temperature
With the summer switch-o option, the return pre-
heating can be suppressed outside the heating pe-
riod. If the heating circuit concerned is controlled by
the controller, the adjustments automatically adapt
to the heating circuit.
Sensor HS Relay
Sensor
Return
Adjustment chan-
nel
Description Adjustment range / selection Factory setting
Relay Relay selection system dependent system dependent
Sen. Return Return sensor selection system dependent system dependent
Sen. HS Heat source sensor selection system dependent system dependent
Ton Switch-on temperature dierence 2.0 ... 30.0 K [4.0 ... 60.0 °Ra] 6.0 K [12.0 °Ra]
To Switch-o temperature dierence 1.0 ... 29.0 K [2.0 ... 58.0 °Ra] 4.0 K [8.0 °Ra]
Summer o Summer switch-o option Yes, No No
Sensor Outdoor sensor selection system dependent system dependent*
To Switch-o temperature 10 ... 60 °C [50 ... 140 °F] 20 °C [68 °F]
Funct. Activation / Deactivation Activ., Deactivated Deactivated
Arrangement / Opt. functions / Add new function... / Ret. preheat.
* When a heating circuit has been activated, this
adjustment is determined by the corresponding
parameter in the heating circuit menu.