62
Heating / HCs / New HC / Internal
Adjustment channel Description Adjustment range / selection Factory setting
HC pump Heating circuit pump system dependent system dependent
Mixer open Relay selection mixer open system dependent system dependent
Mixer closed Relay selection mixer closed system dependent system dependent
Flow sensor Flow sensor selection system dependent system dependent
Sen. Outd. Outdoor sensor selection system dependent system dependent
Heating curve Heating curve 0.3 ... 3.0 1.0
Day correction Day correction -5 ... +45 K 0 K
Towmax Maximum ow temperature 10 ... 100 °C 50 °C
Mode Operation mode Summer o, Ext. switch, both Summer o
TSummer Summer temperature day 0 ... 40 °C 20 °C
Daytime on Daytime on 00:00 ... 23:45 00:00
Daytime O Daytime O 00:00 ... 23:45 00:00
Tnight Summer temperature night 0 ... 40 °C 14 °C
Ext. switch
External switch sensor input selec-
tion
system dependent system dependent
Remote control Remote control option Yes, No No
Sen. Rem.control Remote control sensor input selection system dependent system dependent
Timer Timer option Yes, No No
Mode Timer mode Day / Night, Day / O Day / Night
Night corr. Night correction -20 ... +30 K -5 K
Timer Timer - -
Days of the week Day selection
All days, Monday ... Sunday,
Continue
-
Timer Time frame adjustment 00:00 ... 23:45 -
Room therm. 1 ... 5 Room thermostat option (1 ... 5) Yes, No No
Type Room thermostat type selection Sensor, Switch Sensor
Sen. RTH RTH sensor input selection system dependent system dependent
Troom Room temperature 10 ... 30 °C 18 °C
Timer RTH timer Yes, No, Inactive No