No. PARAMETER SETTING RANGE STANDARD SYSTEM VALUE
1 Enter Code 0000 - 9999 1000
2 Language German
3 Contrast – 10 to + 10 0
4 Display Actual return
5 Emergency operation ON / OFF OFF
6 System type ON / OFF OFF
7 Heat-Up program ON / OFF OFF
8 Summer operation ON / OFF ON
9 Pump cycles ON / OFF OFF
10 Pump constant run ON / OFF OFF
11 Fixed temperature OFF / °C OFF
12 Source Water
13 Source temperature MIN – 10 °C to 10 °C – 5 °C
14 Return temperature MAX 20 °C to 55 °C 50 °C
15 Flow temperature MAX heating 20 °C to 65 °C 60 °C
16 Flow temperature MAX DHW 20 °C to 65 °C 60 °C
17 Mixer temperature MAX 20 °C to 90 °C 50 °C
18 Mixer dynamic 30 - 240 100
19 Frost Protect – 10 °C to 10 °C 4 °C
20 Remote control selection HEAT CIRCUIT 1
21 FE Correction - 5 K bis + 5 K 0
22 Room influence 0 to 20 5
23 On time heat source 2 ON / OFF OFF
24 Heating limit OFF to 30 °C OFF
25 Dual mode temperature - heating – 20 °C to 30 °C 0 °C
26 Off time heat source 2 OFF to 10 h OFF
27 Heating curve gap 1 K to 10 K 3 K
28 Set boiler temperature 60 °C to 100 °C 70 °C
29 On time HS 2 DHW ON / OFF OFF
30 DHW limits OFF to 30 °C OFF
31 Dual mode temperature - DHW – 20 °C to 30 °C 0 °C
32 DHW operation DHW priority
33 DHW auto ON / OFF OFF
34 WW ECO ON / OFF ON
35 DHW stages 1 – 6 1
36 DHW hysteresis 1 °C to 10 °C 3 °C
37 PASTEURISATION ON / OFF OFF
38 Defrost MIN 1 to 20 min 1 min
39 Manual defrost ON / OFF OFF
40 CNTRL RESP TM 1 – 30 10
41 Idle time after switching the compressor OFF 1 to 120 min 20 min
42 Residual idle time
43 QUICK START
44 RELAY TEST
45 LCD TEST
46 ERROR LIST
47 Software version HP
48 Software version IWS
49 Type IWS
50 ANALYSIS
51 DIAGNOSTIC
52 Reset HP (IWS)
53 Run Times
5.8 Commissioning report
The controller should be in standby mode during commissioning. This prevents an uncontrolled heat pump start.
Please remember to reset the system into its last operating mode.