6.1 Specication
WPMW II WPMS II
Supply voltage 230 V ~ ± 10 %, 50 Hz
Power consumption max. 8 VA
EN 60529
EN 60730
Protection IP 21 Protection IP 20
Safety class I Safety class II
Function type 1B
Software - class A
Control panel integration to DIN 43700 Cut-out 138 x 92
Clock backup, day > 10 hours
permiss. ambient temperature during operation 0 to 50 °C
permiss. ambient temperature during storage -30 to 60 °C
Sensor resistances Test resistance with 2000 W
Communication system RS232 (optical), CAN
Max. relay output capacities
Buffer loading pumps 1 and 2 2 (1.5) A
Heating circuit pump 2 (1.5) A
Mixer circuit pump 2 (1.5) A
DHW loading pump 2 (1.5) A
DHW circulation pump 2 (1.5) A
Source pump 2 (1.5) A
Contact HS 2 2 (1.5) A
Mixer 2 (1.5) A
Solar heating pump 2 (1.5) A
max. total relay output capacity 10 (10) A
6.2 Standard settings
At the factory, the heat pump manager is programmed with the following standard settings:
Switching times
1)
for heating circuit 1 and heating circuit 2 H1 / H2 (day mode)
Monday - Friday 6:00 - 22:00
Saturday - Sunday 7:00 - 23:00
ROOM TEMP 1 / 2
2)
Room temperature in day mode 20 °C
Room temperature in setback mode 20 °C
DHW program switching times
Monday - Sunday
3)
22:00 - 6:00 and 8:00 - 10:00
DHW temperature
DHW DAY T 47 °C
DHW SETBACK T 10 °C
Heating curve slope
Heating curve 1 0.6
Heating curve 2 0.2
1) Only for switching times pair 1; switching time pairs 2 and 3 are pre-programmed.
2) Stiebel Eltron recommends systems without night setback; our systems are set up accordingly.
3) 22:00 - 6:00 (night heat-up to take advantage of favourable HP tarifs)
8:00 - 10:00 (heat-up after DHW is drawn off in the morning)