STIEBEL ELTRON WPMW II - Tables; 6.1 Specification; 6.2 Standard settings

STIEBEL ELTRON WPMW II
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
6 Tables
6.1 Specication
WPMW II WPMS II
Supply voltage 230 V ~ ± 10 %, 50 Hz
Power consumption max. 8 VA
EN 60529
EN 60730
Protection IP 21 Protection IP 20
Safety class I Safety class II
Function type 1B
Software - class A
Control panel integration to DIN 43700 Cut-out 138 x 92
Clock backup, day > 10 hours
permiss. ambient temperature during operation 0 to 50 °C
permiss. ambient temperature during storage -30 to 60 °C
Sensor resistances Test resistance with 2000 W
Communication system RS232 (optical), CAN
Max. relay output capacities
Buffer loading pumps 1 and 2 2 (1.5) A
Heating circuit pump 2 (1.5) A
Mixer circuit pump 2 (1.5) A
DHW loading pump 2 (1.5) A
DHW circulation pump 2 (1.5) A
Source pump 2 (1.5) A
Contact HS 2 2 (1.5) A
Mixer 2 (1.5) A
Solar heating pump 2 (1.5) A
max. total relay output capacity 10 (10) A
6.2 Standard settings
At the factory, the heat pump manager is programmed with the following standard settings:
Switching times
1)
for heating circuit 1 and heating circuit 2 H1 / H2 (day mode)
Monday - Friday 6:00 - 22:00
Saturday - Sunday 7:00 - 23:00
ROOM TEMP 1 / 2
2)
Room temperature in day mode 20 °C
Room temperature in setback mode 20 °C
DHW program switching times
Monday - Sunday
3)
22:00 - 6:00 and 8:00 - 10:00
DHW temperature
DHW DAY T 47 °C
DHW SETBACK T 10 °C
Heating curve slope
Heating curve 1 0.6
Heating curve 2 0.2
1) Only for switching times pair 1; switching time pairs 2 and 3 are pre-programmed.
2) Stiebel Eltron recommends systems without night setback; our systems are set up accordingly.
3) 22:00 - 6:00 (night heat-up to take advantage of favourable HP tarifs)
8:00 - 10:00 (heat-up after DHW is drawn off in the morning)