4.5.1 VCT with DeviceNet™ communication (92) continued
DeviceNet™ Wink feature
The Wink feature provides the capability of setting the CLOSED and
OPEN LEDs to simultaneously ash or wink at a 2Hz rate. This feature
aids in physically locating the unit on the network.
1. DeviceNet™ communications are required in order to set the Wink
feature. The unit must be addressed and correctly congured to be
recognized by the control system.
2. Set byte 0, bit 2 to 1 in the desired unit. Once the correct unit
has been physically located on the network, indicated by the
winking of the CLOSED and OPEN LEDs, set byte 0 bit 2 back to0.
Performing this function will not change the closed and open
sensor setpoints.
Quartz with DeviceNet™ Fault Bit (input byte 0, bit 7)
1. The Fault indication will set to a 1 when input byte 0, bits 0 and 1
are set to 1 at the same time.
2. When input byte 0, bits 0 and 1 are both set to 1, this would
indicate that the valve is both open and closed at the same time.
This would be an abnormal or Fault condition.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the StoneL Quartz QX Series and is the answer not in the manual?

StoneL Quartz QX Series Specifications

General IconGeneral
BrandStoneL
ModelQuartz QX Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals