C) INDICATOR ON, FAN ON. LIGHTS FLOAT TO FULL.
POSSIBLE CAUSE
1) Analog line broken or no analog output from console.
SOLUTION
Try control cable for defective pack in a different console output.
Remember that this changes the dimmer numbers, and repatch-
ing may be necessary, as well as resetting the number of dim-
mers. If problem persists, check analog line for breaks. Other-
wise, problem is probably in console.
D) INDICATOR ON. FAN ON. ALL LIGHTS OFF.
POSSIBLE CAUSE
1) Analog line shorted or reversed.
SOLUTION
Repair or clear shorts on analog line, or replace defective con-
trol cable.
E) INDICATOR ON, FAN ON, CONSOLE NOT ADDRESSING DIM-
MERS CORRECTLY
(I.E. DIMMER NUMBERS ARE CONSISTENTLY
OFF BY A CERTAIN NUMBER).
POSSIBLE CAUSE
1) Patch problem in console.
SOLUTION
Check 6kW/12kW assignments in patch.
F) ALL DIMMERS IN ONE PACK WILL ONLY GO TO 90%.
POSSIBLE CAUSE
1) Control wiring error.
SOLUTION
+ Clock and common probably reversed in control wiring.
G) ALL DIMMERS IN ONE PACK WILL NOT GO TO ZERO.
POSSIBLE CAUSE
1) Control wiring error.
SOLUTION
- Clock and common probably reversed in control wiring.