cybercool 2 screw original insTrUcTions
11.4 Option anti-corrosion coating
The aluminium fins of the air side heat exchanger coils are coated with polyurethane.
We recommend this option for an improved protection against corrosion for an installation:
- in an industrial environment
- located near waste incinerators or waste water treatment plants
- near the sea (site within 20 km from the coast).
As the corrosion protection depends largely on the concentration and corrosiveness of industrial exhaust gas
no warranty for a general corrosion resistance can be derived from this.
When using the anti-corrosion coating the cooling capacity specified in the technical data is reduced by
510%.
The airside pressure loss increases by 0 - 5%.