cybercool 2 screw original insTrUcTions
Alarm message Cause for alarm Cause Elimination
High pressure #
failure
triggered
-
Press black release button at HP
switch after elimination of error.
Low pressure #
failure
Low pressure switch has
triggered.
Leak in refrigerant circuit.
Repair the leak. Refill refrigerant.
-
3. Expansion valve defective. Exchange expansion valve.
Power switch comp.
#
has triggered.
continuity and current consumption.
Compressor #
failure
or the protection device has
detected an error.
. Find the exact cause of error.
Sensor # failure
value adjustable in the control-
ler has been exceeded.
-
ues in selected zone.
measuring instrument.
Replace defective sensor.
Sensor # broken
is outside the range defined in
the controller.
thermo meter, pressure gauge. Replace
defective sensor.
EEV #: Pressure
sensor error
expansion valve has detected
a malfunction of the pressure
sensor.
Replace pressure sensor.
EEV #: Temperature
sensor error
-
ed a malfunction of the temper-
ature sensor.
Replace temperature sensor.
# stands for a number in case of several components of the same kind.
8. Malfunction