Modellreihe ESO ... ASN (1) 4302 4602 4702 5102 6002 6602 6702
Max. Außentemperatur (a) °C 43,3 42,0 44,5 43,5 42,0 41,0 43,1
max. Wasservolumenstom (b) m³/h 92 99 106 112 129 139 143
min. Wasservolumenstom (c) m³/h 46 50 53 56 64 65 71
Modellreihe ESO ... ASN (1) 10202 11102 11502 12602 13102 14102
Max. Außentemperatur (a) °C 42,7 41,6 40,9 39,7 40,5 39,6
max. Wasservolumenstom (b) m³/h 223 234 249 266 282 297
min. Wasservolumenstom (c) m³/h 111 117 125 133 141 149
Modellreihe ESO ... ASN (1) 7102 7402 8002 8702 9602 9702 9802
Max. Außentemperatur (a) °C 42,0 43,3 42,3 41,0 39,6 42,8 41,6
max. Wasservolumenstom (b) m³/h 152 163 171 190 205 195 208
min. Wasservolumenstom (c) m³/h 76 81 85 95 102 98 104
Modellreihe ESO ... ASF (2) 4302 4602 4702 5102 6002 6602 6702
Max. Außentemperatur (a) °C 43,3 42,0 44,5 43,5 42,0 40,8 43,1
max. Wasservolumenstom (b) m³/h 99 107 115 121 139 146 154
min. Wasservolumenstom (c) m³/h 50 54 57 60 69 73 77
Modellreihe ESO ... ASF (2) 10202 11102 11502 12602 13102 14102
Max. Außentemperatur (a) °C 42,7 41,6 40,9 39,7 40,5 39,4
max. Wasservolumenstom (b) m³/h 241 253 269 287 304 321
min. Wasservolumenstom (c) m³/h 120 127 135 143 152 160
Modellreihe ESO ... ASF (2) 7102 7402 8002 8702 9602 9702 9802
Max. Außentemperatur (a) °C 42,0 43,3 42,3 41,0 39,6 42,8 41,6
max. Wasservolumenstom (b) m³/h 164 176 184 206 221 211 225
min. Wasservolumenstom (c) m³/h 82 88 92 103 110 105 112
EN/09.2019/G41  © STULZ GmbH – all rights reserved
cybercool 2 screw original insTrUcTions
(1) Water, without free cooling
(2) Water/ethylen glycol 30% (EG30), with free cooling
(a) full load at 18°C/12°C water temperature inlet/outlet
(b) full load at 18°C/14°C water temperature inlet/outlet (min. dTw), outdoor temperature 35°C
(c) full load at 18°C/10°C water temperature inlet/outlet (max. dTw), outdoor temperature 35°C
Air conditions and water volume flows
Minimal outdoor temperature: –10 °C (optionally –40 °C)
Models ESO ... ASN (1)
Max. outdoor temperature (a) °C
max. water volume flow (b) m³/h
min. water volume flow (c) m³/h
Models ESO ... ASN (1)
Max. outdoor temperature (a) °C
max. water volume flow (b) m³/h
min. water volume flow (c) m³/h
Models ESO ... ASN (1)
Max. outdoor temperature (a) °C
max. water volume flow (b) m³/h
min. water volume flow (c) m³/h
Models ESO ... ASF (2)
Max. outdoor temperature (a) °C
max. water volume flow (b) m³/h
min. water volume flow (c) m³/h
Models ESO ... ASF (2)
Max. outdoor temperature (a) °C
max. water volume flow (b) m³/h
min. water volume flow (c) m³/h
Models ESO ... ASF (2)
Max. outdoor temperature (a) °C
max. water volume flow (b) m³/h
min. water volume flow (c) m³/h