77 © STULZ GmbH – all rights reserved EN/09.2019/G41
cybercool 2 screw original insTrUcTions
on the chiller unit type (stated in the table).
- RT
min: minimum runtime of compressor Command:
- Pause: minimum idle time of compressor Command:
- CT
min: minimum cycle time of compressor Command:
min runtime
min idle time
min cycle time
on
off
Compressor operation
comp 1 minruntime 300
comp 1 pause 300
comp 1 mincycle 900
Unit types RTmin Pause CTmin
E_O 3002 to E_O 5102 s 300 300 600
E_O 6002 to E_O 14102 s 300 300 900