91 © STULZ GmbH – all rights reserved EN/09.2019/G41
cybercool 2 screw original insTrUcTions
Alarm message Cause for alarm Cause Elimination
EEV #: Stepper
motor error
-
ed a malfunction of the stepper
motor.
 
 Replace expansion valve.
eev# reliability
alarm (Carel EVD)

reach the valve by the Modbus
connection.
Bus connection to the valve faulty. 
Pump # failure 
also the internal pump fault



Pump motor defective.
-

cable.
watertemp. inlet #
too high

been exceeded.
 



watertemp. inlet #
too low

adjusted limit value.
 



watertemp. outlet #
too high

been exceeded.
 



-
orator by checking the temperature
difference between flow water temp.
and evaporation temperature.

side. Air inlet temperature too high.



condenser by checking the temper-
ature difference between outdoor
air temperature and condensation
temperature.
watertemp. outlet #
too low

adjusted limit value.
 
Phase error Phase monitoring device has
detected an error.
Phase failure. 
Water flow alarm 
limit value set in the flow switch
for minimum flow.
 
 
3. Air in the water circuit. Purge the circuit by the vent valves.
Buserror 
in the bus communication.
-
rectly connected.

Addressconflict A bus address has been
assigned twice.
- 
must be changed.
External alarm in #
failure
No voltage is present at the
digital input for the external
alarm #.

a signal.

 
# stands for a number in case of several components of the same kind.