43 © STULZ SpA . – all rights reserved EN/39B/06.2018
SAL
ATTENTION
Screw anchors included in the kit ACTMKITSO1 are suitable to fix the shelves only to concrete or
brick walls. For other kinds of wall (for instance sandwich type), the most suitable fixing system
must be used. If the above mentioned kit is not used, check that the used shelves are suitable to
support the weight.
DANGER
It's important to prevent hot air expelled by the condenser fan from being even partially sucked
back in. This would cause continuous stoppages, commanded by the pressure switches, reducing
efficiency and increasing electricity consumption. Improper operation of this type can also cause
irreparable harm to the compressor.
Do not obstruct circulation of air being sucked into or expelled from the air conditioner.
Positioning of the free cooling module