INSTALLATION, START-UP & MAINTENANCE MANUAL
MODEL NO.: SD-220 TO SD-600- DDS OPTION
REV 0 – May 24,,.2001
20
SECTION 4 MAINTENANCE
* Advice
In order to ensure continuous and trouble-free operation, a
maintenance contract with
S
S
u
u
l
l
l
l
a
a
i
i
r
r
®
®
is recommended.
Also, the following points should be checked regularly:
Daily
•
Carry out a general visual check and watch out for possible disturbances
during operation.
•
Check function by manually operating the automatic condensate drain on
the pre-filter.
•
Do an optical color test on the blue gel indicator for non-DDS dryers:
Indicator Color Approx. dew point [ °C]
Blue gel
Blue
Pink
Transparent
- 25
0
+ 15
Weekly
•
Check the differential pressure on the pre-filter, which should not exceed
10 PSID. Values greater than this indicate that the filter cartridge must be
changed.
•
Check the differential pressure on the after-filter, which should not exceed
10 PSID. Values greater than this indicate that the filter cartridge must be
changed.
•
Check the backpressure at the silencer placed behind the exhaust valve
combination; it should not exceed 5 PSIG. Use the gauge of the vessel
that is to be regenerated.
•
Drain inlet and exhaust valve chambers using valves provided below the
valve (refer to photo attached).
•
Drain pilot air filter housing of condensate (refer to photo attached).