ShopTek™ ST4, ST5, ST7, ST11, ST15 Three-phase 60 Hz User Manual 4: Installation
88292018-236 R00
Subject to EAR, ECCN EAR99 and related export control restrictions. 37
4.3.1 Pipe sizing
Pipes should be sized as a minimum to match the dimen-
sions of the compressor’s discharge co
nnection. All piping 
and fittings should be rated for the discharge pressure.
4.3.2 Auxiliary receiver tank
An auxiliary receiver tank should be installed in systems 
where large demand fluctuations will occur.
4.3.3 Isolation valves
Install isolation valves where isolation of the compressor 
from the service lines is required. These valves should 
have drip legs that drain at an angle downward from the 
base. A vent to the piping should be installed down-
stream of the compressor outlet connection.
When two compressors are installed to operate in parallel 
with a comm
on receiver tank, an isolation valve and drain 
trap for each compressor should be installed before the 
common separator/sump.
4.3.4 Fluid containment
Compressors have a fluid containment pan to collect fluid 
leaks or spills. The pan has a drain located on the front 
side of the machine.
4.4 Belt check
Tension of drive belts should be checked upon installa-
tion and after ½ to 2 hours of run time. This is essential to 
pr
oper performance of the compressor unit as well as to 
ensure long belt life. In addition, belt tension should be 
checked every 2000 hours and adjusted if necessary.
Refer to Section 6.8: Belt maintenance 
on page 45 for 
detailed instructions.
4.5 Fluid level check
The compressor is shipped fully charged with the proper 
amount of fluid. However, it is necessary to check the fluid 
level at the time of installation and during compressor oper-
ation. Check the fluid level by looking at the sight glass on 
the sep
arator tube when the compressor is in the SHUT 
DOWN MODE (fluid level may not be visible when operat-
ing). In this condition the sight glass should be completely 
full. Add 
fluid if the level is visible or if no fluid is visible at all.
4.6 Electrical preparation
Interior electrical wiring is installed at the factory. 
Required customer wiring should be done by a qualified 
electrician in compliance with OSHA, National Electric 
Code and/or any applicable local electrical codes apply-
ing to isolation switches, fused disconnect
s, etc. Sullair 
provides a wiring diagram for use by the installer. An 
electrical check should be made to ensure that the first 
start-up will be successful. The compressor and drive 
should be properly grounded/earthed in accordance with 
applicable codes, regulations, and requirements.
Feeder cables should be sized by the customer/electrical 
con
tractor to ensure that the circuit is balanced and not 
overloaded by other electrical equipment. The length of 
wiring from a suitable electrical power source is critical 
because voltage drops can adversely effect the perfor-
mance of the compressor. Cable sizes may v
ary consid-
erably so the mains terminals will 
accept up to 120 mm
2
(4/0 awg) (75 kw) cable.
Feeder cable connections to incoming terminals L1-L2-
L3
 should be tight and clean.
The applied voltage must conform to the motor and com-
pressor data plate ratings.
A starter hole is provided for an incoming power connec-
tion. If it is necessary to make a hole 
in the control box in 
a different location, care should be taken to not allow 
metal shavings to enter the starter and other electrical 
components within the box. If another hole is used, the 
original hole must be blocked off with a sealed plug.
1. Check incoming voltage. The incoming volt-
ag
e must match the compressor’s wire rat-
ing/specifications.
2. Check motor starter and overload heater sizes.
3. Check all electrical connections for tightness.
 NOTE
Compressors not equipped with a receiver tank 
may need to have their response times adjusted. 
Contact Sullair Customer Care for assistance.
 WARNING
Energized internal components are a potentially 
fatal shock hazard. Disconnect all power before 
performing any work on the compressor’s elec-
trical system.