Section 1
SUPERVISOR PROTOCOL
3
MESSAGE TYPES
The following messages sent by the sequencing master to slaves:
MESSAGE TYPE FORMAT EXAMPLE
Q - Quick status ##Qxx 01Q4E
S - Stop ##Sxx 01S4C
U - Unload ##Uxx 01U4A
L - Load (Modulate) ##Lxx 01L53
F - Full load ##Fxx 01F59
T - Trim (Modulate) ##Txx 01T4B
E - Emergency Stop ##Exx 01E5A
If a machine is stopped U, L, F or T will start the machine.
The slave response to these messages is:
MESSAGE TYPE FORMAT EXAMPLE
q - Quick status ##q1,2,h,r,mxx 01q0,115,2000,M,C65
1 is Capacity, 2 is P2, h is Run Hours, r is Run Status and m is Mode
RUN STATUS (r)
E - E-Stop
M - Manual Stop m - Manual stop & Common Fault
R - Remote Stop r - Remote stop & Common Fault
B - Standby b - Standby & Common Fault
S - Starting s - Starting & Common Fault
U - Unloaded u - Unloaded & Common Fault
L - Loaded l - Loaded & Common Fault
T - Trim t - Trim & Common Fault
F - Full load f - Full load & Common Fault
MODE (m)
A - Auto run mode, remote start/stop enabled.
a - Auto run mode, remote start/stop disabled.
C - Cont run mode, remote start/stop enabled.
c - Cont run mode, remote start/stop disabled.
The following messages sent by machines when the system is in stand alone sequencing :
MESSAGE TYPE FORMAT EXAMPLE
N - Net status ##N1,2,h,r,mxx 01N0,115,2000,M,C88
M - Monitor Enable ##Mxx 01M52
1 is Capacity, 2 is P2, h is Run Hours, r is Run Status and m is Mode.