Table 4-1B Analog Alarms (LS-16T, LS-20T and LS-20TS Compressors)
Start Run
Sensor Type Limit Delay Delay Check (*) Comment
P_1 Low Fault 5 5 0 When Running Immediate Fault
P_1 High Inhibit 5 0 0 At Start High sump psi at start
P_1 High Fault 500** 0 0 Constantly Sensor failure fault
P_2 High Fault 500** 0 0 Constantly Sensor failure fault
P_3 High Fault 500** 0 0 Constantly Sensor failure fault
P_4 High Fault 500** 0 0 Constantly Sensor failure fault
T_1 Low Fault -40 0 0 Constantly Sensor failure fault
T_1 High Warn 245 5 30 Constantly Delayed for temp spikes
T_1 High Warn 255 0 0 Constantly Immediate Warning
T_1 High Fault 255 5 30 Constantly Delayed for temp spikes
T_1 High Fault 265 0 0 Constantly Immediate Fault
T_1 High Fault 500 0 0 Constantly Sensor failure fault
T_2 Low Fault -40 0 0 Constantly Sensor failure fault
T_2 High Warn 245 5 30 Constantly Delayed for temp spikes
T_2 High Warn 255 0 0 Constantly Immediate Warning
T_2 High Fault 255 5 30 Constantly Delayed for temp spikes
T_2 High Fault 265 0 0 Constantly Immediate Fault
T_2 High Fault 500 0 0 Constantly Sensor failure fault
T_3 Low Warn -40 0 0 Constantly Sensor failure warning
T_3 High Warn 500 0 0 Constantly Sensor failure warning
T_4 Low Fault -40 0 0 Constantly Sensor failure fault
T_4 High Warn 245 5 30 Constantly Delayed for temp spikes
T_4 High Warn 255 0 0 Constantly Immediate Warning
T_4 High Fault 255 5 30 Constantly Delayed for temp spikes
T_4 High Fault 265 0 0 Constantly Immediate Fault
T_4 High Fault 500 0 0 Constantly Sensor failure fault
(*) In the ‘Check’ column above, alarms are checked:
Constantly - if machine running or stopped
When Running - if machine is running
If Enabled - if parameter is non-zero
At Start - will not allow start if alarm present
Over Min Psi - machine is loaded and above min load pressure
(**) 750 psi for 750 psi transducers.

Other manuals for Sullair SUPERVISOR CONTROLLER Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sullair SUPERVISOR CONTROLLER Series and is the answer not in the manual?

Sullair SUPERVISOR CONTROLLER Series Specifications

General IconGeneral
BrandSullair
ModelSUPERVISOR CONTROLLER Series
CategoryController
LanguageEnglish

Related product manuals