SUPERVISOR CONTROLLERâ„¢ USER MANUAL SECTION 4
24
Table 4-4: Parameters
Type Enable Default Min Max Display Text Comment
Setup Always 1 0 2 Press Tran 200,250,500, 750
Setup X200 135 50 225 P1 Max 250psi transducer
Setup X250 135 50 195 P1 Max 200psi transducer
Setup X500 250 150 495 P1 Max 500psi transducer
Setup X750 400 300 560 P1 Max 750psi transducer
Setup Always 0 0 1 Water Switch Water pressure switch enable for water
cooled machines
Setup Flooded 0 0 1 OilSwitch Oil switch enable for flooded screw
machines
Setup Always 65 20 200 Min Load Psi Minimum acceptable Loaded P1 value
Setup Always 0 0 30 Stop Timer If not 0, run unloaded for this time before
stopping
Setup Always 0 0 30 Lube Cycle Prelube/Postlube time
Setup Always 0 0 2 K8 Option Disable, Lube Pump, Master Control
Setup Always 0 0 100000 Load Hours Hours machine has been loaded
Setup Always 0 0 100000 Run Hours Hours machine has been running
Setup Always 0 0 100000 Load Cycles Number of load cycles
Setup Always 0 0 100000 Starts Number of starts
Setup Always 0 0 10000 Capacity Used by monitor to determine system load
Cal Always 0 -7 7 P1
Cal Always 0 -7 7 P2
Cal Always -20 10 dP1
Cal Always 0 -7 7 P3
Cal Always 0 -7 7 P4
Cal Always 0 0 1 Fault on Warn Force shutdown on warning
User X200 110 30 220 Unload 250psi transducer unload pressure
User X250 110 30 185 Unload 200psi transducer unload pressure