SECTION 4 SUPERVISOR CONTROLLERâ„¢ USER MANUAL
25
User X500 150 150 360 Unload 500psi transducer unload pressure
User Always 150 150 560 Unload 750psi transducer unload pressure
User Always 10 3 70 Load Delta Differential pressure from unload pressure
User Always 15 0 59 Unload Time Auto mode shut down after unloaded for
this time
User Always 0 0 30 Drain Interval Time between drains (Minutes)
User Always 0 0 10 Drain Time Duration of drain (Seconds)
User Always 0 0 59 Restart Time Auto restart on power up if not 0 (Seconds)
User Always 0 0 15 Wye Delta Wye to delta starter transition time
(Seconds)
User Always 0 0 2 Language French, German, Italian, Spanish, English
User Always 0 0 1 Temp Units Fahrenheit, Celsius
User Always 0 0 2 Press Units Pressure units, Psi, Bar, kPa
Seq Com
Mod
0 0 4 Sequence by Disabled,Com, Hours, Remote, Slave,
Time Of Day etc.
Seq Always 0 0 100000 Seq Hrs Used for Hours sequencing mode
Seq Always 1 1 16 Com Number Communications ID number
Seq Always 1 1 16 Machines Number of machines in a system
Seq Always 70 20 185 Low Press Panic start next machine in sequence
Seq Always 10 2 59 Recover Time Keeps multiple machines from starting at
same time (seconds)
Seq Always 0 0 250 Rotate Used to force a machine to stop
Table 4-4: Parameters