Section 2
SUPERVISOR II DESCRIPTION
5
2.1 BASIC INTRODUCTION
Refer toFigure2---1. TheSupervisor
II
has a two
linedisplay toshowtemperature, pressure andsta-
tus. It has a keypad for operating the compressor,
programming the control points and selecting dis-
plays. There isagraphic illustration withlamps that
light to show the item being displayed. The lamps
flash if that component is in an alarm condition.
2.2 KEYPAD---ALL MODELS
The keypad is used to control the machine as well
as display status and change setpoints. Refer to
figure 2 --- 1 for following key descriptions.
S
Stop
--- Used to put the machine into
manual stop. It is also used to clear alarm
conditions.
O
S
Continuous
--- Starts machine if no alarm
conditions are present. Also used to clear
alarm conditions whilemachine isrunning.
I
S
Auto
--- Starts machine and selects auto
mode if no alarm conditions are present.
Also used to clear alarm conditions while
machine is running.
S
Display
--- Used to display pressures,
temperatures and other status information
(See section on STATUS DISPLAYS).
DISPLY
S
Logo
--- Used for various functions de-
scribed in later sections
S
Program
--- Used to enter the parameter
change mode where control parameters
may be displayed and changed (See PA-
RAMETER SETUP).
PROG
S
Up arrow
--- Used in status displays to
change displays and in parameter setup
mode to increment a value.
S
Down arrow, lamp test
--- Used in status
displays to change displays and in param-
eter setup mode to increment a value.
When inthe default display thekey willlight
all the lamps for three seconds.
2.3 STATUS DISPLAYS --- SEE 2.3A THROUGH 2.3F
FOR SPECIFIC MODELS
2.3 A STATUS DISPLAYS --- ES --- 8
By default the line pressure (P2) and discharge
temperature (T1) are shown on the bottom line of
the display, and machine status on the top line.
The following are the various machine status mes-
sages that indicate the state of the compressor:
(Display graphics shown below.)
S
STOP
--- Compressor is off.
S
ST ANDBY
--- Compressor isoffbutarmed
tostart. Thisstate maybeentered because
of a power up, or the unload timer had ex-
pired and stopped the machine. NOTE :
The machine may start at any time.
S
STARTING
--- Machine is trying to start.
S
OFF LOAD
--- Machine is running and off
loaded.
S
ON LOAD
--- Machine is running and
loaded.
S
FULL LD
--- Machine is running and fully
loaded. This state is only displayed if the
machine has a full load valve.
S
RMT STOP
--- Compressor is off but
armed tostart. The machine will start when
the remote start contact is closed. NOTE :
the machine may start at any time.
S
SEQSTOP
--- Compressor isoffbutarmed
tostart. The machine will start when the se-
quencing conditions meet the critera to
start. NOTE : the machine may start at any
time.
This default display appears as follows:
STOP
110 180