Chapter 2 Cabinet and Rack Specifications 9
Power Requirements
The AC power sources must provide the correct voltage, current, and frequency
specified on the model and serial number label. The module can run without
interruption within the limits shown in
TABLE 2-6.
Sun Fire Cabinet
This section describes the physical, electrical, and environmental requirements for
the Sun Fire 6800 cabinet.
The floor area at the installation site must provide enough stability to support the
weight of the cabinet and installed trays, sufficient space for installation and
servicing of the cabinet and components, and sufficient ventilation to provide a
free flow of air to the cabinet.
Physical Specifications
TABLE 2-7 provides the physical dimensions of the Sun Fire cabinet.
TABLE 2-6 Sun StorEdge Expansion Cabinet AC Power Requirements
Parameter Requirements
AC voltage rating 200 to 240 VAC
AC voltage range 180 to 264 VAC
Frequency range 50 to 60 Hz
Current at 240 VAC 24A
Power consumption 5.4 kW
TABLE 2-7 Sun Fire Cabinet Dimensions
Height Width Depth Empty Weight
75 in. 24 in. 53 in. 325 pounds
190.5 cm 61 cm 134.6 cm 147 kg