26 Function Parameter Table
E500 Series Universal Low-Power Inverter
Parameter
Type
Function
Code
Name
Setting Range and
Description
Minimum
unit
Default
setting
Modifica-
tion limit
Multispeed and senior running parameter group
F3.11
Under voltage
p
rotection level
180 ~ 230V /
360 ~ 460V
1
200/
400
F3.12
Overvoltage
suppression level
350 ~ 400V /
700 ~ 800V
1
360/
720
F3.13
Current
amplitude
limiting level
150 ~ 250 (%) 1 180
F3.14 Program version 1200 ~ 1299 1 1200
F3.15 Reserve
F3.16 Reserve
F3.17
Multi-speed
running mode
Units: PLC action
selection
0: No action
1: Action
2: Conditional
Tens: PLC
operating mode
selection
0: Single cycle
mode
1:Single cycle
stop mode
2: Final value
keeping mode
3: Set value
keeping mode
4: Continuous cycle
mode
1 0000
F3.18
Stage 1 running
time
0.0S~6000.0S 0.1 0.0
F3.19
Stage 2 running
time
0.0S~6000.0S 0.1 0.0
F3.20
Stage 3 running
time
0.0S~6000.0S 0.1 0.0
F3.21
Stage 4 running
time
0.0S~6000.0S 0.1 0.0
F3.22
PLC multi
-
speed
running directio
n
0000~1111H 1 0000
F3.23
PLC running
scheduled stop
0~9999(min) 1 0
F3.24
Fault
self-recovery
times
0~5 1 3
F3.25
Fault
self-recovery
time
0.0~60.0 0.1 2.0