20 Function Parameter Table
E500 Series Universal Low-Power Inverter
5 Function Parameter Table
Parameter
Type
Function
Code
Name
Setting Range and
Description
Minimum
unit
Default
setting
Modifica-
tion limit
Basic running parameter group
F0.00
Frequency
input channel
0: Digital setting
1: External analog
quantity
2: External
communication
3: Panel
potentiometer
4: Selection of
external terminal
5: Combined setting
1 3
F0.01
Frequency
digital setting
0.0Hz ~ Upper
limiting frequency
0.1 0.0
F0.02
Selection of
running
command
channel and
mode
LED Units:
Selection of running
command channel
0: Keyboard control
1: External terminal
control
2: communication
port
LED Tens: Running
command mode
selection
0: Two-line mode 1
1: Two-line mode 2
2: Three-line mode
3: Special mode for
terminal machine
LED Hundreds:
REV prevention
0: REV prevention
void
1: REV prevention
effective
LED Kilobit:
Power-on auto start
0: Power-on auto
start forbidden
1: Power-on auto
start allowed
1 1000
F0.03
Lower limiting
frequency
0.0Hz ~ [F0.04] 0.1 0.0
F0.04
Upper limiting
frequency
[F0.03] ~ 1000Hz 0.1 50.0
F0.05
Acceleration
time
0.1 ~ 600.0 Sec 0.1 5.0
F0.06
Deceleration
time
0.1 ~ 600.0 Sec 0.1 5.0