EasyManua.ls Logo

Sunfar E500-2S0022(B) - Page 88

Default Icon
103 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
78 SUNFAR Self-Defined Communication Protocol
E500 Series Universal Low-Power Inverter
Data classification
(Sent by main machine)
Feature information (Slave machine response )
6 7 8 9 10 11 12
2
Read program
version of slave
machine
Reserve Reserve # # # #
3
Read operation
information of
slave machine
Main
machine
control
Main
machine
frequency
setting
Reserve Reserve Reserve Reserve
4F Reserve # # # # # #
For example: If the data classification value in the frame sent by main machine
is 0, the
feedback information of slave machine is 400015,which means that 4
represents voltage class–380V; 0 is feature information value; 0015 represents
power–1.5kw.
1.3.2 Command classification 1- Read running parameters of slave machine
Main machine sending frame size is 14 bytes, while slave machine response
frame size is 18 types.
Sent by main machine
0 1 2
3 4 5 6 7 8 9 10 11 12 13
Frame header
Slave address
Slave address
1
Operation command
Operation command
0
Data subentry
Data subentry
Checksum
Checksum
Checksum
Checksum
Frame end
Slave machine response
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Frame header
Slave address
Slave address
Slave machine response
Status feedback
Status feedback
0
Data subentry
Data subentry
Running data
Running data
Running data
Running data
Checksum
Checksum
Checksum
Checksum
Frame end
HRW Limited
admin@hrw.hk
www.hrw.hk

Related product manuals