2nd slot end charging
00:00:00
Setting range: 00:00:00-23:59:00
3rd slot start charging
00:00:00
Setting range: 00:00:00-23:59:00
3rd slot end charging
00:00:00
Setting range: 00:00:00-23:59:00
Timed start discharging
enable
Disable default
Disable this function
Enable
After the time-slot discharge function is enabled, the power
supply mode will change to AC 1ST and the system will switch
to battery inverter power supply only during the set discharge
period or when the mains power is off.
1st slot start
discharging
00:00:00
Setting range: 00:00:00-23:59:00
1st slot end discharging
00:00:00
Setting range: 00:00:00-23:59:00
2nd slot start
discharging
00:00:00
Setting range: 00:00:00-23:59:00
2nd slot end
discharging
00:00:00
Setting range: 00:00:00-23:59:00
3rd slot start
discharging
00:00:00
Setting range: 00:00:00-23:59:00
3rd slot end discharging
00:00:00
Setting range: 00:00:00-23:59:00
Battery setup
Battery type
USER
User-defined, user can set all battery parameter.
SLd
Sealed lead-acid battery.
FLd
Flooded lead-acid battery.
GEL
Gel lead-acid battery.
LFP14/ 15/
LFP 16 default
LFP li-ion battery, L14\L15\L16 corresponds battery cells
number in series.
N13/ N14
Ternary li-ion battery.
Maximum chg. current
200A default
Current setting range:0~200A.
Maximum chg. voltage
57.6V default
Setting range:48V~58.4V, increment of each click is 0.4V,
parameter can be set only when battery type is USER and
L14/15/16,N13/14
Stop discharge voltage
42V default
When the battery voltage falls below this voltage point and
parameter 13 value is reached, the inverter output will be
switched off. Setting range: 40V~48V, increment of each click
is 0.4V, parameter can be set only when battery type is USER
and L14/15/16,N13/14
Stop dchg. delay time
5 default
Indicates the duration when battery voltage reached parameter
12 value in over-voltage procession. Setting range: 5s~50s,
increment of each click is 5s, parameter can be set only when
battery type is USER and LFP14/15/16,NCM13/14
Battery Under Volt
(alarm) Point
44V default
When the battery voltage is lower than this judgment point,
the device will under-voltage alarm, the output will not shut
down, setting range 40V~52V, step 0.4V
Eod recovery voltage
52V default
Battery recover discharge from under voltage protection when
voltage above this value. Setting range: 44V~54V.