53
9. Datasheet
MODEL
SEI-8K-SP
SEI-10K-SP
SEI-12K-SP
Settable
Inverter output
Rated Output Power
8800W
10,000W
12000W
Max. Peak Power
17,600VA
20,000VA
24,000VA
Rated Output Voltage
230Vac(Single phase)(200/208/220/240Vac settable)
Y
Output voltage error
±5%
Load Capacity of Motors
5HP
6HP
6HP
Rated AC Frequency
50/60Hz ± 0.3Hz
Y
Waveform
Pure Sine Wave
Switch Time
10ms(typical)
Overload
After triggering the overload protection the inverter will resume
output after 3 minutes, 5 consecutive overloads will switch off the
output until the inverter is restarted.
(102%<load<110%): alarm and output shutdown after 5min;
(110% < load < 125%) : alarm and output shutdown after 10s.
Load > 125% : alarm reported and output switched off after 5s.
AC OUT(on-grid
Rated Output Power
8800W
10,000W
12000W
Max. Peak Power
8800VA
10,000VA
12000VA
Power factor
0.8 leading to 0.8
lagging
0.8 leading to 0.8
lagging
0.8 leading to 0.8
lagging
Rated voltage
220/230Vac
220/230Vac
220/230Vac
Rated AC Frequency
50/60Hz
50/60Hz
50/60Hz
Rated AC out current
38.2A
43.5A
52.2A
Max AC out current
40A
45.5A
54.5A
THD
<3%
<3%
<3%
Battery
Battery Type
Li-ion / Lead-Acid / User Defined
Y
Rated Battery Voltage
48Vdc ( minimum start-up voltage 44V )
Voltage Range
40-60Vdc
Max. Generator Charging
Current
60A
Y
Max. Grid Charging Current
120A
Y
Max. Hybrid Charging Current
200A
Y
PV input
Num. of MPP Trackers
2
Max. PV array power
5500W+5500W
5500W+5500W
6600W+6600W
Max. input current
22/22A
Max.PV Isc
37A/37A
Max. Voltage of Open Circuit
500Vdc