127
Parameter SG5.0RT SG6.0RT
Display LED
Communication WLAN / Ethernet / RS485 / DI / DO
DC connection type MC4 (Max. 6 mm
2
)
AC connection type Plug and play
Country of manufacture China
* The inverter enters standby state when the input voltage ranges between 1,000 V and
1,100 V. If the maximum DC voltage in the system can exceed 1,000 V, the MC4 connectors
included in the scope of delivery must not be used. In this case MC4-Evo2 connectors must
be used.
** Please note the min. voltage without MPP tracker derating is 303V (+5%) for SG10/15/
20RT and 236V(+5%) for SG5.0/7.0/8.0RT @AC230V 12.5A.
*** The voltage difference between MPPTs should be less than 150 V. The voltage of the
configured string should be higher than the lower limit of the rated MPPT voltage.
**** For inverters without a DC switch, it is necessary to prepare an external DC switch ac-
cording to AS 60947.3.
Parameter SG7.0RT SG8.0RT
Input (DC)
Recommended max. PV in-
put power
10.5 kWp 12 kWp
Max. PV input voltage 1100 V
*
Min. PV input voltage /
Start-up input voltage
180 V / 180 V
Nominal input voltage 600 V
MPP voltage range 160 V–1000 V
**
MPP voltage range for
rated power
260 V – 850 V
***
310 V – 850 V
***
No. of independent MPP
inputs
2
No. of PV strings per MPPT
2 / 1
Max. PV input current 37.5 A (25 A / 12.5 A)
Max. DC short-circuit
current
48 A (32 A / 16 A)
Output (AC)
Nominal AC power (@ 230
V, 50 Hz)
6999 W for "AU", 7000 W
for others
8000 W
Max. AC output power
6999 VA for "AU", 7000 VA
for "BE", "DE", 7700 VA for
others
8000 VA for "AU", "BE",
"DE", 8800 VA for others
User Manual 10 Appendix