User Manual 2 Product Description
23
Note: The local control will be automatically set to ON when a remote control
command is reported to the inverter.
Tab. 2-21 Frequency Protection Parameters in Conditions of SPI (IT)
Explanation
LCD Setting
Remote Control
0 (OFF)
1 (ON)
0
1
Min. frequency 1 (F<) (Hz)
47.50
49.80
47.50
49.80
Min. frequency 1 (F<) tripping time (s)
0.1
0.1
4.0
0.1
Min. frequency 2 (F<<) (Hz)
47.50
47.50
47.50
47.50
Min. frequency 2 (F<<) tripping time (s)
0.1
0.1
4.0
4.0
Max. frequency 1 (F>) (Hz)
51.50
50.20
51.50
50.20
Max. frequency 1 (F>) tripping time (s)
0.1
0.1
1.0
0.1
Max. frequency 2 (F>>) (Hz)
51.50
51.50
51.50
51.50
Max. frequency 2 (F>>) tripping time (s)
0.1
0.1
1.0
1.0
When the local control and remote control modes exist at the same
time, the remote control mode takes priority over the local control
mode.