User Manual 7 LCD Operation
55
E-total: 1999kWh
E-today: 20.0kWh
Ipv: 2.9A
Grid Vtg:
Grid Frq:
221.7V
50.0Hz
Vpv: 250.0V
Pac:
Status:
3456W
Running
* The images shown here are for your reference only. For –D series, both PV1
and PV2 will be displayed.
Tab. 7-2 Status Description
The inverter waits for sufficient sunlight, then the DC voltage
recovers.
The inverter is initializing and synchronizing with the grid.
After being energized, the inverter tracks the PV strings’
maximum power point (MPP) and feeds the AC power to grid.
This mode is the normal mode.
The inverter will stop running by manual “OFF” via the LCD
menu. Set to “ON” if you want to restart the inverter.
The DSP or LCD firmware is upgrading.
If an error occurs, the inverter will automatically stop operation,
trigger the AC relay and show “Error xxx” on the LCD with the
indicator red (xxx is the error code).
Once the error is cleared in recovery time, the inverter will
automatically try to resume normal operation. The recovery
time can be set via the App.
If the device is in standby mode for more than 10 minutes, please
check:
Whether the insolation is sufficient and the PV connection is correct.
If no anomaly is found, disconnect and reconnect the DC switch and
the main switch to restart.
If it still does not work, contact SUNGROW.