User Manual 7 LCD Operation
59
Tab. 7-4 Default Protective Parameters for Countries in Europe
Parameter
DE
BE, LUX,
FR1
FR2
FR3
NL, EU, PL
IT
V
max
(V)
287.5
264.5
255.3
264.5
253.0
264.5
V
min
(V)
184.0
184.0
184.0
195.5
184.0
195.5
1-V
max
(V)
287.5
264.5
255.3
264.5
276.0
264.5
2-V
max
(V)
287.5
264.5
255.3
264.5
287.5
264.5
1-V
min
(V)
184.0
184.0
184.0
195.5
195.5
195.5
2-V
min
(V)
103.5
184.0
184.0
195.5
115.0
195.5
Protection Recover
Vmax-rec (230.0 V299.0 V):
Recovery value for an over-voltage error. Inverter will
start operating when the grid voltage falls below this
value.
Vmin-rec (46.0 V230.0 V):
Recovery value for an under-voltage error. Inverter will
start operating when the grid voltage is above this value.
Vmax-rec: 253.0V
Vmin-rec: 195.5V
Enter Esc
Tab. 7-5 Default Voltage Recover Parameters for Countries in Europe
Parameter
DE
FR
BE
LUX
NL, EU, PL
IT
V
max-rec
(V)
251.0
251.0
251.0
251.0
253.0
251.0
V
min-rec
(V)
195.5
195.5
195.5
195.5
197.5
197.5
10-Minute Over-voltage Protection
ON (default setting): enables the protection function. The inverter will
automatically disconnect from the grid within 3 s when the average voltage for a
10 min period exceeds the set-point of 10 Min Over Vtg.
OFF: disables the function.
Range: 230.0 V264.5 V, 253.0 V by default.
10 Min Vtg: 253.0V
OFF ON Esc
Enter Esc

Table of Contents

Other manuals for Sungrow SG2K5-S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG2K5-S and is the answer not in the manual?

Sungrow SG2K5-S Specifications

General IconGeneral
BrandSungrow
ModelSG2K5-S
CategoryInverter
LanguageEnglish

Related product manuals