Parameter Default value Range
Import Power Limit 43.47kW 0-50kW
The formula used to calculate the import power limit should be: Set value of Import Power
Limit (kW) ≤ 3*230*0.8*rated current of the house's main switch.
8.10.17 Energy Management Mode
Tap Settings→Energy Management Parameters→General Parameters→Energy Man-
agement Mode to enter the screen, as shown in the following figure.