System 13: Solar system with east/west collector fields, 2 tanks, 3-ways valve switch
loading tank
Description:
The controller calculates the temperature
difference between collector sensor T1, T0 and
tank sensor T2, T4. If any difference is larger
than or identical to the adjusted switch-on
temperature difference, then the corresponding
solar circulation pump (R1 and/ or R2) will be
switched on, and simultaneously valve R4 turns
to the corresponding tank and corresponding
tank will be loaded until the switch-off
temperature difference or the maximum tank
temperature is reached.
The priority logic effects prior loading of the tank
1.