Operation manual of solar controller SR1568
Page 35 of 87
System 21: Solar system with 1 collector field, 2 tanks, valve switch loading tank,
preheating return of heating system
Description:
The controller calculates the temperature
difference between collector sensor T1 and
sensor T2 of tank 1, T4 of tank 2. If any difference
is larger than or identical to the adjusted switch-on
temperature difference, then the solar circulation
pump (R1) will be switched on, and
simultaneously valve R4 turns to the
corresponding tank, the tank will be loaded until
the switch-off temperature difference or the
maximum tank temperature is reached.
The priority logic effects prior loading of the tank
1.
Another temperature difference between heat
source T5 and heating return T6 can be used to
control the 3-ways valve R5 to preheat the return
water of heating system by the solar system.