Sutron Corporation X-Link Operations & Maintenance Manual, Rev 1.63 5/24/2016 pg. 112
10 seconds was added to ensure that a reading was not missed due to minor
timing issue. As long as the SDI-12 sensor takes less than 50 seconds to
complete, there should be no issues getting data from both sensors.
8.9.3. Seametrics Result Sharing
If two measurements are setup, one as a Seametrics Flow and the other as a
Seametrics Rate, as long as the Measurement Time and Measurement Interval of
the two are the same, the same reading from the Seametrics flow meter will be
used to complete both measurements.
8.10. Computing Rate of Change
With software version 1.48, several new commands were added to the equation
processor: Prev and DeltaT.
Those commands allow the computation of changes in a sensor reading. For
example, it is possible to compute how many digital counts have ocurred
between two readings. The example below shows how to do exactly that:
Or use the following if the rollover setting is not
zero:
((M1-Prev1)<0)*(M1-Prev1+rollover+1) + ((M1-
Prev1)>=0)*(M1-Prev1)
Where rollover is the value of the rollover setting.
In the example above, M1 has been setup to simply count the incoming digital
pulses. M2 has been setup as Meta of M1 in order to correctly sync the two
measurements, such that M2 waits for M1 to complete.
The equation setup for M2 computes the difference in the current and the
previous readings from measurement M1 (expressed as M1 - Prev1), and divides
it by DeltaT1 which is the amount of time in seconds between the two readings.