18.3.1. Identifying Registers
There are two types of data that can be accessed using the Modbus protocol.
These include Holding and Input registers.
18.3.1.1. Holding Registers
Holding registers are reserved for the purpose of setting and getting data such as
the date and time and diagnostic counts if the ability to send the above
Diagnostic (0x08) command is not available. The following table identifies the
holding registers and their locations. Each of these registers is an unsigned 16-
bit value (if readings registers using an Xpert, set the data type to ushort).
0 – force all active
measurements
1-16 force that
measurement only
*Note: When forcing a measurement, be sure to wait the proper amount of time
for a measurement to finish before requesting data.
18.3.1.2. Input Registers
Input registers return the last measured data from the device. Ideally these
values should be requested on a schedule slightly lagging the measurement
schedule on the X-Link. This will ensure data will follow that found in the X-Link
log. If the last measured data is not acceptable, a live reading can be forced by
writing to the Force Measurement (1010) holding register. Care must be taken