SyScroll Air CO/HP/RE BLN without pump 40 45 50 60 65 75
Rated voltage V/ph/Hz 400V/3/50Hz
Max. absorbed power with pump kW 19 21 25 29 32 36
Max. current FLA A 34 44 46 57 66 84
Max. start-up current LRA A 113 134 142 166 175 217
External fuses A 63 63 63 80 80 100
Max. cable section (*) mm
2
25 25 25 35 35 50
EXCHANGER RESISTANCE
Rated voltage V/ph/Hz 230/1/50
Max. absorbed power W 35
SyScroll Air CO/HP/RE SLN without pump 40 45 50 60 65 75
Rated voltage V/ph/Hz 400V/3/50Hz
Max. absorbed power with pump kW 19 21 24 28
31
35
Max. current FLA A 33 43 45 56 65 83
Max. start-up current LRA A 112 133 141 165 174 216
External fuses A 63 63 63 80 80 100
Max. cable section (*) mm
2
25 25 25 35 35 50
EXCHANGER RESISTANCE
Rated voltage V/ph/Hz 230/1/50
Max. absorbed power W 35
SyScroll Air CO/HP/RE HT/HPF without pump 40 45 50 60 65 75
Rated voltage V/ph/Hz 400V/3/50Hz
Max. absorbed power with pump kW 21 23 27 29 32 37
Max. current FLA A 36 46 48 57 66 84
Max. start-up current LRA A 115 136 144 166 175 217
External fuses A 63 63 63 80 80 100
Max. cable section (*) mm
2
25 25 25 35 35 50
EXCHANGER RESISTANCE
Rated voltage V/ph/Hz 230/1/50
Max. absorbed power W 35
9 - Technical Data