Mainmenuitem
Sub-menuitem1Sub-menuitem2
Explanations
→HolidaysHolidays
(mm:dd)
1:01–01—01–02
2:09–04—09–10
3:01–05—01–05
Setupto24separatepossible
holidayperiodsforafullyear.
Aholidayperiodcanbeany
numberofconsecutivedays
fromoneandupwards.
Thedatesareintheformat:
MM:DD.
Whenthecurrentdatefalls
withinaholidayperiod,the
schedulerwillusethesettings
fortheweekday“Holiday”.
→Manual/Auto
Inthismenutherunningmode
ofalltheconguredoutput
signalsandanumberofcontrol
functionscanbemanually
controlled.
Thesupplyaircontroller's
outputsignalcanbemanually
set(Manual/Auto)toanyvalue
between0and100%.The
temperatureoutputsignalswill
changeaccordinglyiftheyare
inAutomode.Itisalsopossible
tomanuallycontroleachof
thetemperatureoutputsignals
individually.
Sinceleavinganyofthe
outputsinmanualcontrolwill
disruptthenormalcontrol,
analarmwillbegeneratedas
soonasanyoutputissettoa
manualmode.
Supply
Temperature
contr.
Auto
Manualset:
0.0
Setthesupplyairtemperature
to"Auto","On"or"Off".
Settheoutputsignalbetween
0-100%.
TheoutputsY1,Y2andY3,if
inAuto-mode,willfollowthe
signalaccordingtothesetsplit
values.
SAF:Auto
Manualset:
0.0
EAF:Auto
Manualset:
0.0
SetthestartsignalforSAF
(supplyairfan)&EAF(exhaust
airfan)to"Auto,Manual
fullspeed,Manualhalf
speedorManual
Heating
Auto
Manualset:
100.0
SettheheatingtoAuto,
ManualorOff
Setthemanualoutput0-100%
TopvexSR09,11,TR09-15OperationandMaintenanceInstructions
207880
15
SystemairAB