Explanations
Cooling
Water
Settypeofcoolerused.
Water/DX/DXwith
exchangercontrol/Not
used.
Pumpcontrol
P1–Heating
P1–Exchanger
P1–Cooling
Setpumpstoptemperatures
anddelays.
Freecooling
Freecool
active:No
Outd.temp
activation
22°C
Setfreecoolingactiveto"Yes
orNo.
Settheloweroutdoorday
temperaturelimitforthe
activationofthefreecooling
function.Thetemperatureof
thepreviousdayneedstobe
overthesettemperaturein
orderactivatethefreecooling
function.
Outd.temp
night
High:15.0°C
Low:5.0°C
Roomtempmin.
18°C
Settheupperoutdoornight
temperaturelimitforthe
activationofthefreecooling
function
Settheloweroutdoornight
temperaturelimitforthe
activationofthefreecooling
function
Setthelowerroomtemperature
limit.Thetemperatureneedsto
beabovethisvalueforthefree
coolingfunctiontostayactive
Hourfor
start/stop
Freecooling
Start:0
Stop:7
Setthestartandstoptimefor
thefreecoolingfunction
ForexampleStart:0and
Stop:6
meansthatthefreecooling
sequenceisactivebetween
00.00and06.00h.
Timetoblock
heatoutput
afterFree
cooling
60min
Setthedelayinminutesfrom
thetimewherethefreecooling
sequencehasstoppeduntila
possibleheatingsequenceis
initiated,i.e.howlongacooler
roomtemperaturethanset
temperaturecanbeaccepted
Fanoutputwhen
freecooling
SAF:0%
EAF:0%
Setthefanspeedinpercentage
ofthenormalspeedforeach
fanindividuallyduringthefree
coolingsequence
TopvexSR09,11,TR09-15OperationandMaintenanceInstructions
207880
19