Mainmenuitem
Sub-menuitem1Sub-menuitem2
Explanations
Outdoorsensor
placedin
intakechannel
(intakeduct)
No
Setiftheoutdoorsensoris
placedintheintakeductornot.
ChoosebetweenNoandYes
PresetisNo.
→Support
control
Supportcontrol
Active:No
EAFrunning
duringSupport
contr.:Yes
Whenusingthecontrol
functionroomcontrolor
extractairtemperature
control,itispossibleto
utilizesupport-heatingand/or
support-cooling.Minimum
runningtimeissettable0…720
minutes.(factorysetting20
minutes).Choosebetween
“Active:YesorNo”.
(Forstartandstoptemperatures
seethe"Temperature"menu)
Min.runtime
forsupport
ctrl:60min
Settheminimumrunningtime
inminutesforsupportcontrol
→CO2/VOC
Control
CO2/VOCactive
Never
Type:Fan
Min.time:60
min
Inapplicationswithvarying
occupancythefanspeeds
canbecontrolledbytheair
qualityasmeasuredbya
CO2/VOC-sensor.Seeencl.
corrigomanual(CD)fordet.
explanation
SetactivetoNever,Always
orIftimechanneloff.
Setwhatshouldberegulated.
SelecttypeFan
Setthemin.timetheunitis
activatedbytheCO2/VOC
demandfunction
Activation
level
1/2–speed:800
ppm
1/1–speed:
1000ppm
diff:160ppm
Settheactivationlevelat1/2
speed
Settheactivationlevelat1/1
speed
Setalloweddiff.value
→FirefunctionFiredamper
function
Notactive
Operationwhen
alarm
Stopped
SetredampertoNormally
closed/Normally
open/Notactive.
Setbehaviouroftheunit
whenrealarmistriggered
Stopped/Continuous
run/Normalrun/Only
SAF/OnlyEAF.
TopvexSR09,11,TR09-15OperationandMaintenanceInstructions