EasyManua.ls Logo

TEC DG-700 - Chapter 4 Pressure;Flow @ 50 and @ 25 Modes; Mode Summary; Overview of Pressure;Flow @ 50 and @ 25 Modes; Pressure;Flow @ 50 Mode

TEC DG-700
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Pressure/Flow @ 50 and @ 25 Modes
Chapter 4 Pressure/Flow @ 50 and @ 25 Modes
4.1 Mode Summary
Mode
Application
Channel A Display
Channel B Display
Pressure/Flow @ 50 Pa
(PR/ FL @50)
Specialized mode for
one-point Blower
Door building
airtightness test.
Building pressure in Pascals.
Building leakage at 50 Pascals in units
chosen (CFM@50, m
3
/h@50, l/s@50,
in
2
@50, cm
2
@50).
Pressure/Flow @ 25 Pa
(PR/ FL @25)
Specialized mode for
one-point total
leakage duct
airtightness test.
Duct system pressure in Pascals.
Total duct leakage at 25 Pa in units
chosen (CFM@25, m
3
/h@25, l/s@25,
in
2
@25, cm
2
@25).
Note: Appendix A contains Quick Guides for using the DG-700 to conduct one-point building and duct system
airtightness tests using the @50 and @25 features.
4.2 Overview of Pressure/Flow @ 50 and @ 25 Modes
4.2.a Pressure/Flow @ 50 Mode:
The Pressure/Flow @ 50 mode is used to conduct a one-point
Blower Door building airtightness test. In this mode, Channel A
is used to measure building pressure while Channel B is used to
display estimated building leakage at a test pressure of 50
Pascals. The leakage estimate shown on Channel B is
determined by mathematically adjusting the measured air flow
from the selected Blower Door fan using the real-time Channel A building pressure reading and a Can’t Reach
Pressure factor (see Section 4.8 below).
4.2.b Pressure/Flow @ 25 Mode:
The Pressure/Flow @ 25 mode is a specialized mode used for
conducting a one-point total leakage duct airtightness test. In this
mode, Channel A is used to measure duct system pressure while
Channel B is used to display estimated total duct leakage at a
test pressure of 25 Pascals. The leakage estimate shown on
Channel B is determined by mathematically adjusting the
measured air flow from the selected Duct Blaster fan using the real-time Channel A duct system pressure reading
and a Can’t Reach Pressure factor (see Section 4.8 below).
To select the Pressure/Flow @ 50 or @ 25 modes, press the MODE button until the selected operating
mode shown on the gauge display is PR/ FL @50 or PR/ FL @25. When first entering either of these
two modes, the default pressure units on Channel A is Pascals, the default leakage units on Channel B is
CFM @ 50 or 25, and the default time averaging period is 1 second average.
14
Operating Instructions
for the DG700

Table of Contents

Other manuals for TEC DG-700

Related product manuals