38
TECHRSregulator
SelectthisoptionifyouconnectaroomregulatorwithRScommunication.Sucharegulatorenablestheuser
toviewcurrentCHboilerparametersandchangecertainsettingse.g.pre‐setCHboilertemperature,pre‐set
DHWtemperature.
Standardregulator
Selectthisoptionifyouconnectatwo‐stateregulator.Sucharegulatorsendsasignaltothemaincontroller
informingifthepre‐setroomtemperaturehasbeenreachedornot.
CHpumproomregulator
Whenthisoptionisselected,thesignalfromroomregulatorinformingthatthepre‐setroomtemperaturehas
beenreacheddisablestheCHpump.
Roomreg.temp.lower
NOTE
ThisparameterconcernsRSregulator‐decreasefunctionandStandardregulatorandTECHregulator
withRScommunication.
Theusersetsthevalueofpre‐setvalvetemperaturereductionwhichwillbeintroducedwhenthepre‐setroom
temperatureisreached.
Thetemperaturereductionwillnotbelowerthantheminimumpre‐setCHtemperature.
Example:
Pre‐setCHboilertemperature 55°C
Roomreg.temp.lower 15°C
Minimumpre‐setCHboilertemperature 45°C
Pre‐setCHboilertemperatureafterthepre‐settemperature
valuehasbeenreached
45°C
Oncethepre‐setroomtemperaturehasbeenreachedinthebuilding (signalised by the room
regulator),thepre‐settemperatureattheCHboilerwillbereducedto45°C(10°Cdifference)although
thevalueofRoomreg.temp.lowerparameteris15°C.
4.4.10
Fuellevelcalibration
FITTER'S
MENU
FUELLEVEL
CALIBRATION
Fueltankfull
Fueltankempty
Conductingfuellevelcalibrationproperlyenablestheusertoviewthecurrentleveloffuelonthecontroller
screen.
Thefirststepinvolvesfillingthefueltankup
Next,selecttheoptionFueltankfull.Thecontrollerremembersthelevelasfull(100%).
Whenthereisnofuelleftinthetank(afteraperiodofCHboileroperation),selecttheoptionFuel
tankempty.