Timer function
145
Run-on time: The ON signal at the trigger input switches the output on immediately. If the
input drops (OFF), the output remains ON for the duration of the run-on time.
Delay: The ON signal at the trigger input is only passed on to the output when the delay has
elapsed. An OFF signal at the trigger input after the delay has elapsed causes the output to be
switched off immediately.
Minimum runtime: The ON signal at the trigger input switches the output on immediately. If
the input drops during the minimum runtime (OFF), the output remains switched on anyway until the
minimum runtime has elapsed. The output will remain switched on if the trigger input is in status ON
when the minimum runtime has elapsed.