EasyManua.ls Logo

Technische Alternative UVR 16x2

Technische Alternative UVR 16x2
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cooling demand
31
Output variables
Demand
Demand status ON/OFF; selection of the output
T.dem. > T.dem. set
Status ON if the demand temperature T.dem. is higher than the set
temperature T.dem. set + Diff. on.
T.off > T.off set
Status ON if the shutdown temperature T.off is higher than the set
temperature T.off set + Diff. off.
Low end temp. effective
Status ON if the set demand value exceeds the low end temperature
T.dem. max., regardless of the demand status
Minimum runtime ctr
Display of the remaining runtime for the minimum runtime, in seconds
T.gen. > T.gen. min.
Status OFF for as long as shutdown via generator temperature is in
effect
If there is only a demand sensor, the output variable T.off > T.off set is switched by
threshold T.dem. set + Diff. off.
If there is no generator sensor, the output variable T.gen. > T.gen. min. is always set to
status ON.

Related product manuals