Monitoring function
89
Output variables
Error
Status ON after the delay if the monitored value falls below the
minimum value + Diff. on or exceeds the maximum value + Diff. off;
selection of an output; active in all modes.
Minimum value error
Status ON after the delay if the value falls below the minimum value +
Diff. on; selection of an output; active only in the modes Range and
Minimum.
Maximum value error
Status ON after the delay if the value exceeds the maximum value +
Diff. on; selection of an output; active only in the modes Range and
Maximum.
Monitored value
Display of the relevant monitored value A if only one monitored value
is specified, or the AB differential if two monitored values are used.
Min value ctr
Display of a countdown of the time until error message if monitored
value A or the A-B differential has fallen below the minimum value +
Diff. on.
Max value ctr
Display of a countdown of the time until error message if monitored
value A or the A-B differential has exceeded the maximum value +
Diff. on.
If the monitored value falls below or exceeds one of the thresholds, the corresponding delay
timer will start running. The Error is set to ON if, for the duration of the delay, the
monitored value remains below or above the threshold or does not leave the range between
Diff. on and Diff. off.