The output of the heat generator as % to one decimal place; selection
of the analogue output (0-10 V or PWM)
Display of the current set temperature during pasteurisation. If
pasteurisation is not carried out, 5 °C is displayed.
➢ The hold timer counts down during the interval time once the set temperature + Diff. on is
exceeded at the sensor. If the DHW temperature falls below the set temperature + Diff. on
while the hold time is counting down, the hold time countdown will be restarted once the set
temperature + Diff. on is reached again.
➢ If the DHW temperature falls below the set temperature + Diff. on during pasteurisation, the
hold time countdown will be restarted once the set temperature + Diff. off is reached again.
This ensures that the sensor maintains the required temperature continuously.
➢ Generator output: Scaling of the analogue output: 0 = 0.00 V / 1000 = 10.00 V