Tecnomac E5 - USER PARAMETER SETTINGS

Tecnomac E5
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GB
51
USER PARAMETER SETTINGS
Parameter Min. Max. Unit/meas. DEF
PA PASSWORD -99 +99 Number -19
/ = PROBE PARAMETERS
/1 Cell probe calibration -10 +10 °C 0
/2 Evaporate probe calibration -10 +10 °C 0
/3 Core probe calibration -10 +10 °C 0
/8 Temperature scale (0=Fahrenheit 1=Celsius) 0 1 Flag 1
c = CHILLING / FREEZING
c0 Cell probe differential 1 15 °C +3
c1 Duration of timed chilling and max. duration for chilling by temperature 0 400 min 90
c2 Chilling end set point (core probe) -55 +99 °C 3
c3 Positive storage set point (cell probe) -55 +99 °C 2
c4 Duration of timed freezing and max. duration of freezing by temperature
(when c4=0, key and freezing function to -18°C are disabled.
For chilling units only.) 0 400 min 240
c5 Freezing end set point (core probe) -55 +99 °C -18
c6 Negative storage set point (cell probe) -55 +99 °C -25
c8 Positive and negative chilling duration countdown start temperature -55 +99 °C +65
cA Core probe readout (readout only) --- --- °C ---
cb Set point for SOFT blast chilling (cell probe) and during second stage
of HARD blast chilling -55 +99 °C -5
cd HARD chilling set point (temperature transition HARD ->SOFT of core probe) -55 +99 °C 2 0
cF Cell set point during first stage of HARD blast chilling (core probe) -55 +99 °C -20
d = DEFROST
d0 Defrosting interval (0 = no defrost) 0 99 hours 8 h
dA Defrost probe readout (readout only) --- --- °C ---
U = INPUTS + VARIOUS
u5 Duration of UV lamp activation (if u5=0, UV key is disabled) 0 99 min 0
uA Print interval (when uA=0, HACCP key is disabled) 0 99 min 20