J
Julie ReidAug 8, 2025
What to do if my Tecnoware UPS is beeping twice every second?
- EErin GreenAug 8, 2025
If your Tecnoware UPS is beeping twice every second and the icons are flashing on the LCD display, it indicates that the UPS is overloaded. You should remove some of the devices connected to the UPS output to reduce the load. If devices connected to the UPS are fed directly by the mains via the Bypass, you should still remove excessive loads from the UPS output. If the UPS is locked in Bypass mode after repetitive overloads, first remove the excess loads, then shut down the UPS and restart it.